Efficiency standards in the Southwest region
The DOE Southwest region covers 4 jurisdictions. For split-system air conditioners under 45,000 Btu/h the minimum is 14.3 SEER2, and at 45,000 Btu/h and above it is 13.8 SEER2. The standard is enforced by date of installation, so a contractor cannot legally install a non-compliant unit here. Heat pumps are the exception — they only have to meet the nationwide standard, wherever they are installed.
- Jurisdictions
- 4
- AC <45k Btu/h
- 14.3 SEER2
- AC ≥45k Btu/h
- 13.8 SEER2
- Enforced by
- Installation
Which states are in the Southwest region?
DOE divided the country by population-weighted heating degree days. The Southwest region covers 4 jurisdictions:
Arizona · California · Nevada · New Mexico
The Southwest is the "hot-dry" region, and the only one carrying an additional EER2 requirement — EER measures peak-load performance, which matters most where there are many extreme-heat days.
What minimums apply in the Southwest region?
| Capacity | SEER2 | EER2 |
|---|---|---|
| less than 45,000 Btu/hr | 14.3 | 11.7 / 9.8 |
| 45,000 Btu/hr and above | 13.8 | 11.2 / 9.8 |
| single-package units — air conditioners | — | 10.6 |
- The 11.7 EER2 standard applies to products with a certified SEER2 less than 15.2. The 9.8 EER2 standard applies to products with a certified SEER2 greater than or equal to 15.2.
- The 11.2 EER2 standard applies to products with a certified SEER2 less than 15.2. The 9.8 EER2 standard applies to products with a certified SEER2 greater than or equal to 15.2.
Heat pumps are different. Regional standards do not apply to heat pumps. A heat pump only has to meet the nationwide standard, wherever it is installed. The nationwide minimum for a split-system heat pump is 14.3 SEER2 and 7.5 HSPF2.
How is the standard enforced here?
In the Southeast and Southwest, the standard for split-system air conditioners is based on the date of installation. A unit installed on or after January 1, 2023 must meet the new standard. It is illegal for a contractor to install a product that does not meet the regional standard.
This is the part that surprises homeowners: in these two regions what matters is when the unit was installed, not when it was built. An older non-compliant unit cannot legally be installed here, even if it is sitting in a warehouse.
The legal definition of "installation" (10 CFR 430.2): "Installation of a central air conditioner" means the connection of the refrigerant lines and/or electrical systems to make the central air conditioner operational.
If you believe a non-compliant unit was installed for you, DOE takes reports at [email protected].
What actually drives the cost?
We publish no national average price, and the reason matters: an average across every house, region and system type is not a number you can act on. A replacement that includes duct modification, an electrical upgrade and a permit is a different job from a straight swap, and both read as “system replacement” on a one-page proposal.
What actually drives your number:
- Equipment capacity and tier, which should come from the Manual J rather than the old nameplate.
- The ducts — whether they can move the air the new equipment needs, and what it costs if they cannot.
- Electrical work, if a circuit or panel change is required.
- Permit and inspection, usually required.
- Refrigerant — current equipment uses R-454B or R-32; remaining pre-2025 R-410A stock may price differently.
Which efficiency numbers can you actually compare?
If you are comparing efficiency figures, check which generation they belong to first. On January 1, 2023 DOE changed the test procedure and renamed three metrics: SEER became SEER2, EER became EER2, and HSPF became HSPF2. The current procedure measures at a higher external static pressure, much closer to what equipment meets once installed in a real house on real ductwork.
DOE is explicit about the consequence: “Although SEER2, HSPF2, and EER2 ratings are similar to ratings using the original metrics, they are not directly comparable. Compliance with the new standards for each model must be determined based on its measured SEER2, HSPF2, or EER2.” In practice: a SEER figure from a 2019 article cannot tell you whether a quote reading SEER2 is good, bad or identical.
That is why we publish no conversion factor. We do not publish a SEER-to-SEER2 conversion factor. DOE states that ratings on the new metrics are "not directly comparable" to ratings on the original metrics, and that compliance must be determined from the measured SEER2, EER2 or HSPF2 value. Approximate multipliers circulate widely, but they vary by equipment type and configuration, and using one to compare an old article's number against a number on today's quote is how homeowners end up believing they were offered less efficiency than they were. Compare like with like: ask for the SEER2 figure, and check it against the AHRI certificate.
The nationwide minimum for a split-system air conditioner is 13.4 SEER2, and for a split-system heat pump 14.3 SEER2 with 7.5 HSPF2. What each metric measures · minimums by region and state.
How is the right equipment size decided?
Nearly every persistent comfort problem traces back to equipment size, and size is decided before the first box arrives. The standard is the ACCA Manual J load calculation (ANSI/ACCA 2 Manual J - 2016), which totals the heat gain and loss of your specific house: orientation, window area and type, insulation levels, air infiltration, internal gains, and your local design temperature.
What a Manual J is not: square feet per ton, and not the old unit's tonnage. The first ignores everything that makes one house different from another. The second assumes whoever sized the old equipment got it right, and propagates their error for another fifteen years.
Oversized equipment reaches the setpoint and shuts off before it has dehumidified, so the house ends up cold and clammy at the same time. Every start is also the hardest moment in a compressor's life, so wear accelerates. And you pay for the surplus capacity twice — once to buy it and again to run it.
Ask for the completed Manual J in writing, not the claim that one was done. What it contains and how to read it.
What should a bid show you?
Three bids rarely quote the same job, so comparing headline price compares three different things. The one that was done properly shows its work, and you can check it line by line:
- Model numbers for the outdoor unit, indoor coil, and air handler or furnace.
- The AHRI reference number for that exact combination. A rating applies to a matched system, not to an outdoor unit on its own.
- The SEER2 and, on a heat pump, the HSPF2 of that combination.
- The Manual J result the sizing came from.
- The measured static pressure and any duct work included.
- The permit, and who pulls it.
- Labour warranty, separate from parts, and whether registration is required.
How can you verify any of this yourself?
Everything regulatory on this site traces to a primary source and carries the date it was read: DOE for efficiency standards, EPA for refrigerants and Section 608, the IRS for tax credits, and ACCA for load calculation. The sources for this page are listed at the end with the date each was consulted.
If you find a different figure elsewhere, check two things before deciding which to believe: whether the page says which generation its efficiency metric belongs to, and whether it carries a visible review date. Most of the outdated content in this category fails both tests.
Sources (2)
- U.S. Department of Energy — Central Air Conditioners — Conservation Standards guidance (Final, October 5, 2022) (accessed 2026-08-17)
- Code of Federal Regulations — 10 CFR 430.32(c) — Energy conservation standards for central air conditioners and heat pumps (accessed 2026-08-17)